Servicii

Detectie incendiu

Centrala alarmare incendiu adresabila Siemens FC722-ZE

  • The FC722-ZE (2-loop, expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 252 addresses. The fire control panel can be used as a stand-alone version or networked. It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.
  • All detector lines are monitored for ground faults.
  • Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.
  • Detection and automatic read-in (auto configuration) of all C-NET devices, providing immediate simple operation.
  • Stored data can be uploaded via Cerberus-Remote access.
  • The FC722-ZE is ideally suited for medium-sized applications, e.g. in workshops, hotels, etc. or when networked as part of much larger applications. The FC722-ZE with flexible cross-linking possibilities can also be used for extensive systems.
  • With 48 indicators groups, each with one red and one yellow LED.
  • The expansion and accessories must be ordered separately.
  • Detector compatibility: Cerberus PRO FD720
  • Number of addresses: max. 252
  • Number of detector lines: 2 (4) loops or 4 (8) stub line
  • Programmable input/output: 8
  • Supervised output: 1 x RT alarm 1 x RT fault 1 x horn
  • Mains voltage: 230 VAC
  • Operating voltage: 21... 28.4 VDC
  • Operating current: max. 5 A
  • Power supply: 150 W
  • Emergency power supply: up to 72 h (optional)
  • Battery capacity: 2 x 12 V, 26 Ah
  • Plug-in position: 2 -> for serial interfaces RS232, RS485 , 2 -> for network modules , 1 -> for loop extension (C-NET)
  • Operating temperature: -8... +42 °C
  • Storage temperature: -20... +60 °C
  • Relative humidity: 95% (no condensation)
  • Protection category: IP30
  • Color housing/cover: grey, RAL 7035/grey, RAL-Design 050 00 00
  • Cabinet dimensions (W x H x D): 430 x 796 x 160 mm (without cover cap) 430 x 796 x 188 mm (with cover cap)

Sisteme control acces si avertizare incendiu

Pentru mai multe detalii nu ezitati sa ne contactati.

Contact!