Servicii
Detectie incendiu
Centrala alarmare incendiu adresabila Siemens FC724-ZE
- The FC724-ZE (4-loop, expandable to 8) is a compact fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 504 addresses. The fire control panel can be used as a stand-alone version or networked. The control panel can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.
- All detector lines are monitored for ground faults.
- Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.
- Detection and automatic read-in (auto configuration) of all C-NET devices, providing immediate simple operation.
- Stored data can be uploaded via Cerberus-Remote access.
- The FC724-ZE is ideally suited for large-sized applications, e.g. in industrial plants, regional banks, office complexes, etc. The FC724-ZE with flexible cross linking possibilities can also be used for extensive systems.
- The expansion and accessories must be ordered separately.
- Detector compatibility: Cerberus PRO FD720
- Number of addresses: max. 504
- Number of detector lines: 4 (8) loops or 8 (16) stub lines
- Programmable input/output: 12
- Supervised output: 1x RT alarm 1x RT fault 2x Horn
- Mains voltage: 230 VAC
- Operating voltage: 21... 28.6 VDC
- Operating current: max. 5 A
- Power supply: 150 W
- Emergency power supply: up to 72 h (optional)
- Battery capacity: 2 x 12 V, 26 Ah
- Plug-in position: 2 -> for serial interfaces RS232, RS485 , 2 -> for network modules , 2 -> for loop extension (C-NET)
- Operating temperature: -8... +42 °C
- Storage temperature: -20... +60 °C
- Relative humidity: 95% (no condensation)
- Protection category: IP30
- Color housing/cover: grey, RAL 7035/grey, RAL-Design 050 00 00
- Cabinet dimensions (W x H x D): 430 x 796 x 160 mm (without cover cap) 430 x 796 x 188 mm (with cover cap)